FM200 Fire System Cylinder In fire safety, FM200 fire system cylinders play a critical role in protecting valuable assets and lives across commercial and residential properties. Known for their quick response time, minimal environmental impact, and effectiveness in safeguarding sensitive equipment, FM200 systems are highly regarded. This guide will walk you through everything you need to know about FM200 fire system cylinders, including how they work, their benefits, applications, and how to select the right system for your needs.
What is an FM200 Fire System Cylinder?
FM200 Fire System Cylinder is a vital component of a clean agent fire suppression system. This system quickly suppresses fires without damaging sensitive equipment. FM200, also called HFC-227ea, is a chemical compound used in these systems. The FM200 cylinder stores the agent in a pressurized container, which is often placed in areas where traditional fire suppression methods, such as water sprinklers, may cause damage. Typical locations for these systems include data centers, server rooms, and telecommunication facilities.
How Does the FM200 Fire System Cylinder Work?
FM200 fire systems release the chemical agent into the protected area as soon as a fire is detected. The FM200 cylinder emits the agent as a fine mist, which absorbs heat from the fire. This reduces the heat, stopping the combustion process and extinguishing the fire. The FM200 agent disrupts the chemical reactions that keep fires burning. Since it leaves no residue, it is ideal for protecting delicate equipment and materials.
The system activates when heat or smoke detectors detect a fire. Then, the control panel triggers the release of the FM200 agent into the designated area. This process takes only seconds, minimizing the damage and ensuring the protection of valuable assets in areas like IT rooms, server rooms, and archives.
Benefits of Using FM200 Fire System Cylinders
- Fast-Acting: FM200 systems suppress fires in under 10 seconds. This rapid response minimizes damage and reduces risks to people and property.
- Environmentally Friendly: FM200 is a clean agent with low global warming potential (GWP). It does not deplete the ozone layer, making it safer for both people and the environment.
- Non-Damaging to Equipment: Unlike water-based suppression systems, FM200 will not damage sensitive electronics, electrical equipment, or documents. As a result, it’s perfect for data centers, telecommunications, and electronics manufacturing facilities.
- Minimal Cleanup: FM200 systems leave no residue behind, eliminating the need for cleanup after activation. This is especially valuable in spaces where minimizing downtime is critical.
- Versatile Applications: FM200 systems are effective in many different environments, including offices, libraries, industrial plants, and museum storage areas. This versatility makes FM200 suitable for both residential and commercial properties.
Applications of FM200 Fire System Cylinders
- Data Centers and Server Rooms: These spaces house critical and sensitive equipment. FM200 provides rapid, efficient fire suppression that helps protect servers and computers without causing damage.
- Telecommunications Facilities: In telecommunication exchanges and data transmission centers, FM200 ensures uninterrupted service while safeguarding valuable equipment.
- Archives and Libraries: Libraries and archives house irreplaceable documents and records. FM200 protects these assets from fire while leaving them undamaged.
- Manufacturing and Industrial Plants: In industrial settings with high fire risks, FM200 provides effective protection, preventing damage to machinery and equipment.
- Museums and Art Galleries: Museums and galleries rely on FM200 systems to protect priceless artifacts and artwork from fire damage. Since FM200 won’t harm these items, it offers a safe solution.
Key Features of FM200 Fire System Cylinders
- Cylinder Sizes: FM200 cylinders are available in different sizes, which are suitable for various areas. Larger spaces may require multiple cylinders or larger ones for full coverage.
- Control Panel Integration: FM200 cylinders work seamlessly with fire alarm systems that include heat and smoke detectors. The detectors trigger the system when they detect a fire, ensuring a quick and automatic response.
- Pressure and Discharge: The cylinder stores FM200 in liquid form under pressure. When released, it turns into a gas, rapidly dispersing throughout the protected space.
- Certified and Approved: FM200 systems meet global safety standards and certifications, such as UL, FM, and NFPA, ensuring their reliability and effectiveness.
How to Choose the Right FM200 Fire System Cylinder
- Size of the Protected Area: The area that needs protection is the primary factor in selecting the appropriate FM200 cylinder size. Larger spaces require either multiple cylinders or a larger-capacity cylinder to ensure proper coverage.
- Risk Assessment: Before choosing a system, assess the fire risks in the area. A detailed risk assessment will help you determine the best FM200 fire suppression system for your specific needs.
- System Compatibility: Ensure that the FM200 system integrates with your existing fire detection and alarm systems. The control panel should work seamlessly with heat and smoke detectors to activate the system when necessary.
- Cylinder Placement: The FM200 cylinder should be installed in a location where it can discharge the agent effectively. Consider factors such as ventilation, airflow, and the layout of the protected space when deciding where to place the cylinder.
- Maintenance and Inspection: Regular inspections and maintenance are essential for FM200 systems to ensure proper operation. Check the cylinders for pressure, functionality, and any potential damage.
FM200 Fire System Cylinder FAQs
1. How long does it take for FM200 to suppress a fire?
FM200 systems can extinguish fires in under 10 seconds. The fast response time is critical for limiting fire damage and preventing injury.
2. Is FM200 safe for humans?
Yes, FM200 is safe for humans when used in recommended concentrations. It’s widely used in occupied spaces without significant health risks.
3. How often should FM200 cylinders be serviced?
FM200 systems should be inspected at least annually. Depending on the manufacturer’s recommendations, maintenance typically occurs every 3-5 years.
4. Can FM200 be used outdoors?
FM200 is primarily designed for indoor use, especially in areas with sensitive equipment. Outdoor installations are generally not recommended unless specified.
Conclusion
FM200 Fire System Cylinder offer a fast, effective, and environmentally friendly way to protect valuable assets from fire damage. Their ability to suppress fires quickly, without leaving residue or causing harm to sensitive equipment, makes them an ideal choice for data centers, telecommunications, historical archives, and more. By understanding their benefits, applications, and how to select the right system, you can ensure that your property has the best fire protection available.
Product Information:
Specification:
No. | Specification | Technical Parameter | |
1 | Filling pressure | 4.2Mpa | 5.6Mpa |
2 | Scale of Protective region for one zone | Area:max single-zone is 800m² volume:max single-zone is 3600m³ | |
3 | Spraying time | 10s | |
4 | Filling density | ≤950kg/m3 | ≤1080kg/m3 |
5 | Power | DC24V/1.6A | |
6 | Nitrogen Pressure of Driving Device | 6.0±1.0Mpa(20℃) | |
7 | Condition of reserving room for container | temperature: -10~50℃, relative humidity: ≤97% | |
8 | Max working pressure | 5.3Mpa | 8.0Mpa |
9 | Min working pressure | 4.2Mpa | 4.6Mpa |
10 | Capacity | 90L, 120L, 150L, 180L |